논문명 |
온돌난방에서 경량기포콘크리트의 재료배합에 따른 방열성능 평가 / Evaluation of Thermal Output in the Radiant Floor HeatingDue to the Mixture of Materials in a Lightweight Foamed Concrete |
저자명 |
임재한(Lim Jae-Han) |
발행사 |
대한건축학회 |
수록사항 |
대한건축학회논문집 계획계, v.24 n.2 (2008-02) |
페이지 |
시작페이지(305) 총페이지(8) |
ISSN |
12269093 |
주제분류 |
환경및설비 / 재료 |
주제어 |
온돌 ; 바닥복사난방 ; 방열량 ; 경량기포콘크리트//Ondol ; Radiant Floor Heating ; Thermal Output ; Lightweight Foamed Concrete |
요약1 |
본 연구에서는 온돌난방에서 경량기포콘크리트의 배합조건에 따른 방열량 특성을 분석하는 것을 연구목표로 하였다. |
요약2 |
Normally, the lightweight foamed concrete is used for insulation layer and levelling layer in radiant floor heating. By changing the ratio of ingredients such as an admixture, the fundamental properties of the lightweight foamed concrete could be changed. Due to the conductivity of this material, the characteristics of thermal output could be changed. So this study was aimed to evaluate the thermal output in radiant floor heating due to the mixture of materials in an aerated concrete. Firstly, the current foreign standards regarding the thermal output of radiant floor heating were reviewed. Nextly, the conductivity of lightweight foamed concrete was measured when the admixture and stabilizing agent were added for performance improvements. Finally, thermal output and downward heat loss were evaluated by changing the design parameter such as pipe spacing and water temperature differences. As the results, we could conclude that the conductivity of lightweight foamed concrete could be lowered by 0.12W/mK compared to the KS F 4039. Also the downward heat loss could be lowered by 20%. |
소장처 |
대한건축학회 |