논문명 |
현행 다중이용시설 환기량 기준의 수요기반 환기량 조절법(DCV)에 대한 적용성 평가 / Possibility of Demand Controlled Ventilation (DCV) in Multi-Purposed Facilities under the Current Korean Ventilation Standard |
저자명 |
정재원(Jeong Jae-Weon) ; 노상태(No Sang-Tae) |
발행사 |
대한건축학회 |
수록사항 |
대한건축학회논문집 계획계, v.24 n.3 (2008-03) |
페이지 |
시작페이지(249) 총페이지(8) |
ISSN |
12269093 |
주제분류 |
환경및설비 |
주제어 |
환기량 기준 ; 수요기반 환기량 조절법 ; 외기전담시스템 ; 이산화탄소 ; 전자테그//Ventilation Standard ; Demand Controlled Ventilation ; Dedicated Outdoor Air System ; CO2 ; RFID |
요약1 |
본 연구에서는 현행 우리나라 다중이용시설 환기량기준의 DCV에 대한 적용성을 가상의 모델공간을 대상으로 한 시뮬레이션을 통해 정량적으로 분석하고, 가까운 장래에 DCV가 우리나라 건물에 널리 적용될 때를 대비하여 현행기준의 DCV에 대한 적용성 향상 방안을 제시하고자 한다. |
요약2 |
The objective of this paper was to show the possibility of demand-controlled ventilation (DCV) using the current Korean ventilation standard for multi-purposed facilites. Two attractive DCV approaches; CO2-DCV and RFID-DCV were applied to DCV simulations for a theoretical public assembly space served by a dedicated outdoor air system (DOAS) with enthalpy recovery device. A numerical model for predicting realtime occupant number, ventilation rate, CO2 and formaldehyde (HCHO) concentration under given conditions was developed using a commercial equation solver program. It was found that the current ventilation standard causes unstable ventilation system control in DCV applications, especially under CO2-DCV. It is because the ventilation rate (per person) used in Korea is the sum of the outdoor air required to remove or dilute air contaminants generated by both occupant and building itself, and not a pure function of occupant numbers. Finally, it makes DCV control unstable when ventilation flow is regulated only by the number of occupants. In order for solving this problem, current Korean ventilation standard was modified as a form of ASHRAE Standard 62.1-2007 showing good applicability to various DCV approaches. It was found that this modification enhances applicability of the current ventilation standard to DCV significantly and can maintain acceptable HCHO concentration during the whole operating hours. Fan energy Reduction can also be expected from DCV operations. |
소장처 |
대한건축학회 |