논문명 전압변동에 따른 비상경보설비의 음향특성에 관한 실험적 연구 / An Experimental Study on the Acoustic Characteristics of Fire Alarm Sound due to Voltage Variation
저자명 백은선 ; 백건종 ; 신훈 ; 장길수
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집, v.3 n.1 (2009-03)
페이지 시작페이지(10) 총페이지(6)
주제분류 환경및설비
주제어 Fire Alarm System(화재경보음시스템) ; Sound Pressure Level(음압레벨) ; Fire Equipment(소방설비) ; Fire Safety(화재 안전)
요약2 In this study, voltage variation effects on sound level of fire alarm system were examine in the anechoic room and free field condition. Followings are results. Within the voltage band of ±20% from 24V(center) which is standard voltage, the sound pressure level is considered to be stable but in the condition of -20% below standard voltage, adequate sound pressure level is not assured. Acoustic equipment which is far from receiver can not fulfill standard sound pressure level output due to voltage dropping and this could cause a problem that fire alarm could not be heard to inhabitants.