뒤로 원문보기 | 미리보기 [ 원문보기시 소비되는 포인트 : 100 포인트 ]
논문명 기존 보육시설에 실내공기질 향상을 위한 관리 및 개선방안 / Methods for Management and Improvement of Indoor Air Quality in Child Care Centers
저자명 임지혜(Lim Ji-Hye) ; 손장열(Sohn Jang-Yeul)
발행사 대한건축학회
수록사항 대한건축학회논문집 계획계, v.26 n.09 (2010-09)
페이지 시작페이지(227) 총페이지(10)
ISSN 12269093
주제분류 환경및설비
주제어 보육시설 ; 실내공기질 ; 실내공기질 개선 ; 공기청정기 ; 건축마감자재 ; 환기설비//Child Care Center ; Indoor Air Quality ; Improvement Work for IAQ ; Air Purifier ; Interior Finishing Material ; Ventilation System
요약2 The purpose of this paper is to suggest effective methods for improving and managing IAQ in child care center. Measurements were performed for air temperature, relative humidity, carbon dioxide, fine particle mass, formaldehyde and volatile organic compounds in 17 child care center. In order to analyze the change in concentration of pollutants by time slot, the IAQ was assessed three times before children came to the childcare facilities, and in the morning and afternoon in 6 centers. The improvement works that each child care center took for IAQ were installation of air purifiers, changing interior finishing material, installation of ventilation system. To evaluate the effect of the improvement works, measurements and survey were performed again. In most child care rooms, the indoor pollutant concentration was higher than in outdoor air, indicating the cause of higher indoor air pollution was due to internal sources. The concentration of CO2 and TVOC exceeded the standard, by 37% respectively and the concentration of PM10 and HCHO exceeded the standard, by 23% respectively in all rooms. CO2 and PM10 concentrations tended to be the lowest before children came, increased after they came and decreased again in the afternoon due to children’s breathing and physical activities. TVOC and HCHO concentration peaked before the children came, which got accumulated in the air while the child care facilities are not in use and decreased gradually as time passed. Installing an air purifier in the child care room was effective in decreasing TVOC concentration and installing a ventilation system is effectively decreases PM10, TVOC and HCHO. Changing interior finishing material was not effective at all in decreasing indoor air pollutants during researching term. About 41% of respondants gave a positive response before the improvement work for the question of satisfaction with indoor air in the center and about 87% gave a positive response after the improvement work.
소장처 대한건축학회
스크랩하기
추천문헌 이 논문을 열람하신 아우릭 회원님들이 많이 열람하신 논문을 추천해 드립니다.
[특집] 국내 친환경 건축물 사례 분석
정지나 ; 김용석 ; 이승민 - 그린빌딩(한국그린빌딩협의회지) : v.9 n.1 (200803)
Blower Door를 이용한 국내 주거용 건물의 기밀도 실측 사례 분석
권오현(Kwon Oh-Hyun) ; 김진효(Kim, Jin-Hyo) ; 김민휘(Kim Min-Hwi) ; 석윤진(Seok Yoon-Jin) ; 정재원(Jeong Jae-Weon) - 대한건축학회논문집 계획계 : v.26 n.07 (201007)
보육시설의 실내공기질에 관한 현장측정 및 설문조사 연구
박정하(Park Jung-Ha) ; 박진철(Park Jin-Chul) ; 이언구(Rhee Eon-Ku) - 대한건축학회논문집 계획계 : v.27 n.3 (201103)
[시론] 4차 산업혁명 시대, 건축의 대응
이명식(Lee, Myung-Sik) - 건축(대한건축학회지) : Vol.61 No.05 (201705)
초고층 공동주택 거주자들의 전열교환형 환기장치 운전방식 현황 조사 및 문제점 분석
김진효(Kim Jin-Hyo) ; 조현(Cho Hyun) ; 이종인(Lee Jong-In) ; 김유신(Kim Yu-Sin) ; 정재원(Jeong Jae-Weon) - 대한건축학회논문집 계획계 : v.25 n.02 (200902)
저탄소 시대의 친환경건축물 기술/사례
조욱희 - (사)한국그린빌딩협의회 창립 10주년 기념대회 : (201004)
어린이집 실내환경 실태조사 연구 (1)
김건우 ; 전현도 ; 박진철 - 대한건축학회 학술발표대회 논문집 : (200910)
보육시설에서 공기청정기와 환기가 실내공기질에 미치는 영향
나재성 ; 임지혜 ; 손장열 - 대한건축학회 학술발표대회 논문집 : (200810)
사무소건물에서의 실내공기질 개선에 따른 경제적 효과에 관한 연구
권경우(Kwon Kyung-Woo) ; 박준석(Park Jun-Seok) - 대한건축학회논문집 계획계 : v.23 n.10 (200710)
그린리모델링 현황과 만족도 및 에너지 절감효과 분석
임지혜(Lim, Ji-Hye) ; 한학규(Han, Hak-Gyu) ; 강동렬(Kang, Dong-Ryeol) - 대한건축학회논문집 구조계 : Vol.33 No.09 (201709)